iVECTOR iVECTOR Technical Information
19
iVECTOR Performance Data
The unit must be sized to match the calculated heat loss
requirement of the room with the unit operating at normal fan
speed. The higher fan speeds will be used automatically when
the room temperature is significantly lower than the preset
temperature.
When establishing the temperature difference, i.e. mean water to
room temperature, allowance should be made for temperature
drop in the system. It is the temperature at the convector which
dictates the output.
Model Fan Speed
Heat Output (watts)
Temperature Difference
(°C)
Heat Output (Btu/h)
1824 704
2556 935
3682 1358
2606 905
3632 1283
5149 1883
3224 1086
4448 1804
6521 2376
3842 1267
5265 2324
7894 2869
4460 1448
6082 2845
9266 3363
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
iV60x080
iV60x100
iV60x120
iV60x140
iV60x160
6223 2402
8721 3190
12563 4633
8892 3088
12392 4378
17568 6425
11000 3705
15177 6155
22250 8107
13109 4323
17964 7929
26934 9789
15218 4941
20752 9707
31616 11475
ΔT50 (75-65-20) ΔT20 (45-35-20) ΔT50 (75-65-20) ΔT20 (45-35-20)
Relative Humidity: Sensible cooling at 50%.
Heating Performance Data
Model Fan Speed
Cooling Performance (watts)
Condition 7-12-27
Temperature Difference
(°C)
Cooling Performance (Btu/h)
Condition 7-12-27
707 527
1126 829
1648 1227
1011 753
1600 1178
2304 1716
1250 931
1960 1442
2918 2173
1490 1110
2320 1707
3533 2631
1729 1288
2679 1972
4147 3088
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
iV60x080
iV60x100
iV60x120
iV60x140
iV60x160
2412 1798
3842 2829
5623 4187
3450 2569
5459 4019
7861 5855
4265 3177
6688 4920
9956 7414
5084 3787
7916 5824
12055 8977
5899 7395
9141 6728
14150 10536
Total Sensible Total Sensible
Cooling Performance Data
The intelligent, electronic control system in every iVECTOR provides
a wide range of easy to use heating and cooling operating options. Its
two-tier level of programming incorporates an ‘easy’ mode for everyday
operation and a ‘full’ mode for more advanced functions.
Intelligent and easy to use controls.
l
Each iVECTOR is individually
programmable
l
24/7 programmer with 1 hour
time periods
l
Lockable LCD backlit display
l
Automatic and manual options
for control of fan speeds
l
Option to link to building
management systems
l
Night set-back function