HI-LINE Range Technical Information HI-LINE Range Technical Information
25
HI-LINE RC Performance Data
(continued)
HI-LINE LV Performance Data
This model should only be selected if the normal fan speed
output is capable of maintaining the calculated heat losses of the
room at the chosen operating conditions. This will enable the
boost fan speed and the higher temperature differences to be
used to greater advantage for rapid warming of the room from
cold in excessive conditions.
When establishing the temperature difference, i.e. mean water to
room temperature, allowance should be made for temperature
drop in the system. It is the temperature at the convector which
dictates the output.
Noise Levels
Noise levels tested in accordance with EN 23741.
Model
Sound Pressures at 2.5m (dBA)
20-14 33.3 38.7 45.4
15-10 28.8 35.4 45.6
10-6 23.5 30.8 37.2
7-4 23.4 32.5 43.3
Normal Medium Boost
Weight, Water Content and Motor Power
Model
Motor
Power (W)
Water
Content (l)
Unpacked
Weight (kg)
20-14 80 0.77 14.7
15-10 62 0.56 11.3
10-6 35 0.32 8.9
7-4 35 0.30 7.4
Approximate Hydraulic Resistance
Litres/h
7-4
1084
798
350
134
10-6
1240
657
327
105
15 -10
1500
905
450
157
20 -14
1774
1140
565
221
7-4
9.4
7.7
3.5
1.4
10-6
12.12
6.42
3.25
1.1
15 -10
14.7
8.9
4.37
1.57
20 -14
17.42
11.2
5.5
2.1
455
340
227
113
mm wg kPa
Heating Performance Data
Model Fan Speed
Heat Output
(watts)
Temperature Difference (°C)
Heat Output (Btu/h)
352 541 734 930 1128
645 991 1344 1702 2065
Normal
Boost
7-4
1201 1846 2504 3173 3849
2201 3381 4586 5807 7046
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
Heat outputs tested in accordance with BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply by 1.06.
227 ltr/h (50 gal/h) multiply by 0.96.
113 ltr/h (25 gal/h) multiply by 0.85.
Air Flow
Model
Normal
285
207
143
81
Medium
371
276
171
105
Boost
431
333
220
133
Normal
10061
7307
5048
2859
Medium
13096
9743
6036
3707
Boost
15214
11755
7766
4695
20-14
15-10
10-6
7-4
Air Flow (m
3
/h) Air Flow (ft
3
/h)
HI-LINE RC Performance Data
The unit must be sized to match the calculated heat loss
requirement of the room with the unit operating at normal fan
speed. The higher fan speeds will be used automatically when
the room temperature is significantly lower than the preset
temperature.
When establishing the temperature difference, i.e. mean water to
room temperature, allowance should be made for temperature
drop in the system. It is the temperature at the convector which
dictates the output.
Model Fan Speed
Heat Output (watts)
Temperature Difference
(°C)
Heat Output (Btu/h)
1313 2018 2737 3468 4207
1658 2548 3457 4380 5314
1882 2889 3917 4959 6014
931 1431 1941 2459 2984
1054 1620 2197 2783 3376
1397 2147 2913 3690 4477
610 937 1271 1610 1953
742 1140 1546 1959 2376
954 1467 1990 2521 3059
352 541 734 930 1128
489 752 1020 1292 1568
645 991 1344 1702 2065
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
20-14
15-10
10-6
7-4
4479 6884 9339 11831 14354
5657 8695 11796 14944 18130
6421 9858 13364 16921 20519
3176 4881 6622 8390 10180
3596 5526 7496 9496 11519
4767 7327 9939 12590 15274
2081 3197 4337 5493 6664
2530 3889 5276 6683 8108
3256 5005 6790 8602 10437
1200 1845 2504 3172 3849
1669 2565 3480 4410 5350
2199 3380 4585 5808 7046
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
Model Fan Speed
Temperature Difference
(°C)
Cooling Performance (Btu/h)
1256 1034 1922 1291 2676 1421
1510 1241 2312 1597 3220 1759
1601 1363 2449 1770 3408 1879
886 761 1355 1002 1886 1091
958 815 1466 1058 2041 1123
1276 1093 1953 1434 2719 1549
578 490 884 635 1230 668
646 545 988 704 1375 736
780 638 1194 867 1662 1098
318 274 487 362 678 396
473 405 725 531 1009 574
574 459 878 623 1222 790
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
20-14
15-10
10-6
7-4
4285 3528 6558 4405 9131 4848
5152 4234 7889 5449 10987 6002
5463 4651 8356 6039 11628 6411
3023 2597 4623 3419 6435 3722
3269 2781 5002 3610 6964 3832
4354 3729 6664 4893 9277 5285
1972 1672 3016 2167 4197 2279
2204 1860 3371 2402 4692 2511
2661 2177 4074 2958 5671 3746
1085 935 1662 1235 2313 1351
1614 1382 2474 1812 3443 1958
1958 1566 2996 2126 4169 2695
Tot. Sens. Tot. Sens. Tot. Sens.
15° 20° 25° 15° 20° 25°
Tot. Sens. Tot. Sens. Tot. Sens.
Heat outputs tested in accordance with BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.06.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Cooling performance tested in accordance with BS 4856 Part 2.
Flow Rate: 340 ltr/h.
Relative Humidity: 50%.
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.06.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Heating Performance Data
Cooling Performance Data (Heater/Cooler Model Only)
Cooling Performance (watts)
For combined heating and cooling applications, a suitable chilled
water source and associated controls must be provided and
installed, in accordance with the recommendations of the chiller
manufacturer.
Provision must be made for condensate disposal, in accordance
with any local regulations. A condensate collection tray is fitted
and a suitable drain pipe should be connected to the spigot
(15mm) at the base of the condensate tray.
Thermostatic control for cooling may be achieved by connection
of a thermostat into the mains supply to the unit.
All pipework must be wrapped with anti-condensate material
5-10mm thick.