KICKSPACE
®
Technical Information KICKSPACE
®
Technical Information
13
KICKSPACE
®
Performance Data
Heat outputs tested in accordance with BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.03.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Duo (Hydronic/Electric) Heating Performance Data - Electric Mode
The unit will operate on either fan speed to provide 1kW of heating.
ltr/h
500 600 800 Floor 600-12V 500 Duo 500 600 800 Floor 600-12V 500 Duo
455 788 1046 911 448 1046 652 7.7 10.3 8.9 4.4 10.3 6.4
340 488 625 544 258 625 380 4.8 6.1 5.3 2.5 6.1 3.7
227 231 326 258 136 326 204 2.3 3.2 2.5 1.3 3.2 2.0
113 82 95 82 54 95 68 0.8 0.9 0.8 0.5 0.9 0.7
Approximate Hydraulic Resistance
Model
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
500
Normal 393 566 733 896 1056 1340 1930 2501 3057 3603
Boost 447 683 923 1166 1412 1524 2331 3150 3980 4817
600
Normal 467 729 1000 1278 1562 1592 2486 3412 4361 5330
Boost 607 939 1279 1625 1977 2072 3203 4363 5545 6744
800
Normal 747 1077 1396 1707 2012 2550 3675 4763 5824 6864
Boost 845 1289 1738 2192 2649 2885 4397 5930 7478 9039
Floor
Normal 283 448 622 802 987 965 1530 2122 2736 3366
Boost 483 755 1035 1322 1615 1650 2574 3531 4510 5510
Heat Output (watts) Heat Output (Btu/h)
Hydronic Heating Performance Data
Heat outputs tested in accordance with BS 4856 Part 1.
Hydronic Models
It is preferable to select the model with an output capable of
maintaining the calculated heat losses of the room when
operating at normal speed. This will enable the boost fan speed
and the higher temperature differences to be used to greater
advantage for rapid warming of the room from cold in excessive
conditions.
When establishing the temperature difference, i.e. mean water to
room temperature, allowance should be made for temperature
drop in the system. It is the water temperature at the convector
which dictates the output.
mm wg
kPa
Temperature Difference (°C)
Fan
Speed
Model
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
600 - 12V
Normal 467 729 1000 1278 1562 1592 2486 3412 4361 5330
Boost 607 939 1279 1625 1977 2072 3203 4363 5545 6744
Heat Output (watts) Heat Output (Btu/h)
Low Voltage Hydronic Heating Performance Data
Heat outputs tested in accordance with BS 4856 Part 1.
Temperature Difference (°C)
Fan
Speed
Model
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
500 Duo
Normal 273 447 636 835 1043 930 1527 2169 2849 3560
Boost 372 597 835 1083 1340 1269 2037 2849 3696 4571
Heat Output (watts) Heat Output (Btu/h)
Duo (Hydronic/Electric) Heating Performance Data - Hydronic Mode
Temperature Difference (°C)
Fan
Speed
KICKSPACE
®
Performance Data (continued)
Available Finishes: White, Chrome, Brass, Brushed Stainless.
All remote wall switches are supplied with 3 metres of cable.
All models are equipped to facilitate direct wiring.
Suitable for uses with standard single gang surface or recessed
mounting box (not supplied). The switch must only be used to
operate a single KICKSPACE
®
unit.
For use on Hydronic and Hydronic-Electric (Duo) models only.
Not suitable for Electric only models.
N.B: When a remote wall switch is fitted, the fan speed control switch
on the KICKSPACE
®
facia grille becomes inoperable and must be
disconnected.
Model
Motor
Power (W)
Water
Content (l)
Unit Weight
(kg)
Air Flow
Model
Normal NormalBoost Boost
Noise Levels
Weight, Water Content and Motor Power
Model
500 25.7 38.1
600 26.4 37.2
800 28.5 49.8
Floor 27.4 56.1
600-12V 29.4 39.0
500 Duo 25.7 38.1
Sound Pressures at 2.5m (dBA)
Normal Boost
Air Flow (m
3
/h) Air Flow (ft
3
/h)
KICKSPACE
®
Remote Wall Switch (optional)
500 25 0.26 4.3
600 40 0.30 5.0
800 40 0.34 5.5
Floor 28 0.15 5.5
600-12V 40 0.30 7.9
*
500 Duo 25 0.26 4.5
500 70 90 2471 3177
600 106 138 3742 4872
800 139 210 4908 7415
Floor 76 169 2684 5968
600-12V 106 138 3742 4872
500 Duo 70 90 2471 3117
Air Flow
Model
Low LowHigh High
Air Flow (m
3
/h) Air Flow (ft
3
/h)
500E 70 90 2471 3177
600E 210 N/A 7560 N/A
Electric Heating Performance Data
Model
Low HighMedium
Heat Output (watts)
500E 1000 N/A 2000
600E 1000 2000 3000
* Includes transformer
Noise Levels
Noise levels tested in accordance with EN 23741.
Model
Sound Pressures at 2.5m (dBA)
500E 27.2 40.2
600E 38.0 N/A
Low High
Weight
Model
Unit Weight
(kg)
500E 3.0
600E 3.5
Noise levels tested
in accordance with
EN 23741.
Electric Models
The remote room thermostat is supplied white as standard and is
suitable for 500, 600 & 800 Hydronic models.
KICKSPACE
®
Remote Thermostat
KICKSPACE
®
models 500, 600, 800, 600-12V, 500 Duo and 500E
are supplied with a White (RAL 9003) grille. All these models are
also available in Brown (RAL 8017), Black (RAL 9011), Chrome,
Brushed Stainless Steel and Aluminium. The 600E facia grille is
an integral part of the product and can not be removed and is
supplied with either a White or Brown grille. The floor unit
model is only available with a Beige grille.
KICKSPACE
®
Grille Colour Options
24050 Fan Convector bro 06/12/2011 10:52 Page 13
Vue de la page 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 17 18

Commentaires sur ces manuels

Pas de commentaire