LO-LINE RC Performance Data (continued)
32
LO-LINE RC Technical Information LO-LINE RC Technical Information
33
Noise Levels
Model
Sound Pressures at 2.5m (dBA)
19-15 27.2 31.8 38.6
14-10 23.1 28.5 40.1
9-6 21.6 29.6 38
6-4 23.7 31.7 40.7
Normal Medium Boost
Weight, Water Content and Motor Power
Model
Motor
Power (W)
Water
Content (l)
Unpacked
Weight (kg)
19-15 80 0.75 15.7
14-10 62 0.56 12.7
9-6 35 0.32 9.1
6-4 35 0.3 7.7
Noise levels tested in accordance with EN 23741.
Approximate Hydraulic Resistance
Litres
mm wg kPa
455 910 998 1240 1670 8.98 9.85 12.20 16.40
340 514 520 719 954 5.06 5.10 7.00 9.40
227 235 121 324 469 2.35 1.18 3.20 4.60
113 47 97 75 77 0.45 0.97 0.75 0.82
6-4 9-6 14-10 19-15 6-4 9-6 14-10 19-15
Units are supplied with an electronic infra-red remote control
system with the following features:
l
Automatic room temperature control.
l
Fan only option for ambient air circulation.
l
Three fan speeds.
l
Unit mounted controls and display.
l
Unit control panel electronic tamper proof lock.
l
Displayed temperature calibration system.
Water connections (15mm compression) are on the left-hand
side and the system pipework may be brought in from
underneath or the rear.
LO-LINE RC Water Connections
LO-LINE RC Dimensions and Fixings
All LO-LINE models require an electrical supply of 220-240V –
50Hz fused at 3A.
LO-LINE RC Electrical Data
LO-LINE RC Controls
Model
Dimensions (mm)
19-15 1138 1018 974
14-10 854 733 681
9-6 645 526 481
6-4 523 404 359
ABC
Air Flow
Model
Normal
241
160
112
65
Medium
288
200
129
86
Boost
335
288
175
122
Normal
8507
5648
3954
2295
Medium
10166
7060
4554
3036
Boost
11826
10166
6178
4307
19-15
14-10
9-6
6-4
Air Flow (m
3
/h) Air Flow (ft
3
/h)
Case fixing screw positions and water connections
l
Minimum installation height is 150mm to the underside of
the unit.
l
Maximum ceiling height is 3m.
l
Minimum side clearance is 100mm.
LO-LINE RC Performance Data
It is preferable to select the model with an output capable
of maintaining the calculated heat losses of the room when
operating at normal speed. The higher fan speeds will be used
automatically when the room temperature is significantly lower
than the preset temperature. When establishing the temperature
difference, i.e. mean water to room temperature, allowance
should be made for temperature drop in the system. It is the
temperature at the convector which dictates the output.
For combined heating and cooling applications, a suitable chilled
water source and associated controls must be provided and
installed, in accordance with the recommendations of the chiller
manufacturer.
Provision must be made for condensate disposal, in accordance
with any local regulations. A condensate collection tray is fitted
and a suitable drain pipe should be connected to the spigot
(15mm) at the base of the condensate tray.
Thermostatic control for cooling may be achieved by connection
of a thermostat into the mains supply to the unit.
All pipework must be wrapped with anti-condensate material
5-10mm thick.
Heat outputs tested in accordance with BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.06.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Cooling performance tested in accordance with BS 4856 Part 2.
Flow Rate: 340 ltr/h (75 gal/h).
Relative Humidity: 50%.
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.06.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Model Fan Speed
Heat Output (watts)
Temperature Difference
(°C)
Heat Output (Btu/h)
1509 2221 2921 3613 4298
1731 2548 3351 4144 4930
1938 2852 3751 4640 5520
993 1461 1922 2377 2828
1223 1800 2367 2928 3483
1448 2131 2803 3467 4124
567 834 1098 1358 1615
743 1093 1437 1777 2114
936 1377 1811 2240 2665
383 564 741 916 1090
436 641 843 1043 1241
600 883 1162 1437 1710
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
19-15
14-10
9-6
6-4
5150 7578 9967 12327 14665
5907 8692 11432 14140 16822
6613 9731 12799 15831 18834
3388 4986 6558 8111 9649
4173 6140 8076 9989 11884
4942 7272 9564 11829 14073
1935 2847 3745 4633 5512
2534 3728 4903 6064 7213
3194 4699 6180 7643 9092
1307 1923 2528 3126 3718
1486 2187 2876 3558 4233
2049 3014 3965 4904 5834
20° 30° 40° 50° 60° 20° 30° 40° 50° 60°
Heating Performance Data
Model Fan Speed
Temperature Difference
(°C)
Cooling Performance (Btu/h)
1340 1104 2002 1345 2734 1452
1464 1203 2187 1511 2987 1632
1533 1305 2291 1656 3128 1725
877 754 1310 969 1788 1034
1032 878 1542 1113 2106 1159
1228 1052 1835 1347 2505 1427
499 423 745 535 1018 553
600 507 896 639 1223 655
710 581 1061 770 1448 957
321 277 480 357 655 383
391 335 585 429 798 454
496 397 741 526 1012 654
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
Normal
Medium
Boost
19-15
14-10
9-6
6-4
4572 3767 6831 4589 9328 4954
4995 4105 7462 5156 10192 5568
5231 4453 7817 5650 10673 5886
2992 2573 4470 3306 6101 3528
3521 2996 5261 3798 7186 3955
4190 3589 6261 4596 8547 4869
1703 1443 2542 1825 3473 1887
2047 1730 3057 2180 4173 2235
2423 1982 3620 2627 4941 3565
1095 945 1638 1218 2235 1307
1334 1143 1996 1464 2723 1549
1692 1355 2528 1795 3453 2231
Tot. Sens. Tot. Sens. Tot. Sens.
15° 20° 25° 15° 20° 25°
Tot. Sens. Tot. Sens. Tot. Sens.
Cooling Performance Data (Heater/Cooler Model Only)
Cooling Performance (watts)
24050 Fan Convector bro 06/12/2011 10:53 Page 33
Vue de la page 16
1 2 ... 12 13 14 15 16 17 18

Commentaires sur ces manuels

Pas de commentaire